what size orifice to use with 407c in a 5 ton
-
067 sized piston, unit of measurement calls for 070. Is this enough to cause issues?
I work at a University, and am fighting a reoccurring issue with a residential split system non keeping up when temps become into the mid eighty's and upwardly.
Unit of measurement is a 3 ton R410 I.C.P. unit, fixed orifice.
Indoor unit calls for a 070 piston. This piston in it is 067. Condenser only references TXV, doesn't specify a piston size.
Subcool is approx x, superheat is in the 40's. Comp amp draw is below RLA, suction pressure is low (gauges show a twenty degree gyre, merely no ice or sweating is occurring), and head pressure is slightly low.According to my research, every bit I'm non familiar with a "normal subcool, high superheat" scenario, this indicates a "mild restriction with excess refrigerant", which makes sense because the guy earlier me crammed freon in thinking it was but low.
And so the piston is a 067 instead of a 070, but the evap coil is also fairly dirty, AND the filter drier looks like the installer never replaced it when he did the R-22 to R-410 install. I'm wondering if these 3 issues could be compounding to create a "mild restriction" like situation where the unit loses efficiency when the temps get higher. So my main question is, would you replace the piston with a 070? Obviously I'll clean the evap scroll and supervene upon the drier, but I'1000 wondering if I should get ahead and wait for a 070 piston to get here as well, or is information technology OK to just put the 067 back in and let it go. I was thinking most a TXV, merely this thing has very little room for one and I don't desire the arrangement down any longer than it needs to exist, as the apartment is occupied.
Thanks for any advice you tin give.
-
Usually, the right sized piston comes with the new condenser. Me personally, I change the piston everytime unless it'south an exact lucifer in the gyre already. Seeing that you lot switched from an R22 to a R410A system, it should accept been changed anyway. If y'all tin get a .070 piston, y'all should alter it. Change the filter drier and clean the inside coil. Check your pressures afterwards that.
Sent from my SM-G930P using Tapatalk
-
Post Likes - one Likes, 0 Dislikes
-
I would take some before and after readings, to compare such as temperature difference, pressures, amp.reading etc at similar OD temperatures if possible.
Final edited by Bazooka Joe; 05-04-2017 at 02:22 PM.
-
Post Likes - 2 Likes, 0 Dislikes
-
everything is low even temp split.. I wonder what that means.
-
ten� subcooling is kind of low for a system with fixed metering, and certainly doesn't hint at a brake.
All of the symptoms you mentioned point to an under accuse.
A 0.067 orifice is about right for a 3 ton 13SEER R-410A system, or at least really shut, depending on which manufacturers chart you look at.
Mostly you should ignore the orifice size listed on the indoor coil, and become with what the outdoor unit calls for, which in this case is a TXV.
Since you don't have a TXV, the next closest thing you tin can do is look at a generic chart, and most of them I have at hand testify 0.067 to 0.070, so there isn't actually anything significant to be gained by irresolute the orifice.
-
Post Likes - ane Likes, 0 Dislikes
kdang liked this post.
-
what ICP model # ? If its a 14seer go with txv subsequently cleaning evap/blower wheel & replacing drier . If its a 13 so with a clean scroll shouldn't exist a problem with a 67 vs a lxx
-
Originally Posted by mark beiser
I was taking a 10 caste subcool to exist "normal", because when I worked for a residential service HVAC company, they ever made usa "accuse the unit to 10 degrees subcool unless unit specifies otherwise". Based on the unit'southward chart on the panel, with our outdoor temps fluctuating wildly in TX correct now, 10 degrees subcooling was pretty shut to what it wanted. At this point I'm only going to adjust the charge and monitor it through the summer.
-
Originally Posted past oldguy1949
-
Originally Posted past BrownPigeonSwag
Thank you.Sent from my iPhone using Tapatalk
__________________________________________________ _______________________�Experience is a hard instructor considering she gives the test start, the lesson afterward" ~ Vernon Constabulary
"It's what y'all learn later on yous know information technology all that counts." ~ John Wooden
"When the teachers become unteachable we're all in trouble" ~ Mr. Bill "Think "Pro" is only a proper name, it's not always a mindset determined to do everything correctly" ~ Mr. Bill
-
Post Likes - ane Likes, 0 Dislikes
-
The Lennox charging charts always used subcool for pistons. Ran xiv-16 at 65 ambient and went down as it got hotter out No idea why they have to be so ass backwards from everyone else.
-
every bit you know sc cool should be about 15 on piston depending on ambient weather of class.
-
Originally Posted by Mr Nib
Originally Posted by Mr Bill
As well, the master reason is that when a unit gives me some really strange symptoms that come and get, specially with inefficiency, and it'southward non electrical, I like to just have all the data. Well-nigh every troubleshooting chart I look at asks for superheat, subcool, amp depict, temp splits, outdoor and indoor, temp. So I merely endeavour to get ALL of that, regardless of expansion device. Can't hurt, as far as I'grand concerned.
-
Always take both. As each one can also point to a problem the other doesn't isn't showing. but generally SH for piston, and SC for TXV.
-
Post Likes - v Likes, 0 Dislikes
-
OK, well subsequently getting back over in that location, I think I may take the situation figured out, with help and communication from this thread.UPDATE:
My data, when input into my troubleshooting chart I employ, pointed to a "mild restriction with excess refrigerant". That is all fine and swell, except for the SOURCE of the information was incorrect. I'd misread the condenser charging chart, and incorrectly calculated x degrees subcooling every bit my "required subcooling". Later some of your comments, I reread through the equipment literature and discovered the actual subcooling should be 14 degrees. Then, instead of a "normal subcool/high superheat" condition, I had a "low subcool/high superheat" condition (undercharge). I couldn't find anything indicating how to accuse this unit based on superheat, equally it only said to refer to condenser charging nautical chart and get by its piston size, only then the condenser says TXV and doesn't mention anything nearly charging by superheat. And so I said spiral all this bullcrap and shoved refrigerant in it until I had a 40 degree evap coil, then checked and found I had correct at 14 degrees subcool with about 16 degrees superheat.Now if I can merely verify what the superheat should exist on this unit, I think I'll have information technology nailed downwards. The room render temp is about 73 (Tstat shows room temp at 71), and outdoor air temp is about 77, with a 40 degree evap coil.
-
Need to know indoor wetbulb to calculate what the Sh should be. As information technology changes by the indoor wetbulb and outdoor dry seedling temp.
-
Post Likes - 2 Likes, 0 Dislikes
-
For Time to come Reference:
Originally Posted past BrownPigeonSwag
- Heating type (EH, Gas, Propane, Oil)
- Equipment (Packaged, Split)
- Cooling but, Oestrus Pump,
- Metering device (TXV, Cap tube, orifice)
Here is a list of operating data to evaluate Air conditioning cooling performance:
- RA temp DB
- SA temp DB
- RA temp WB (to calculate ID Relative Humidity...Target 50% RH)
- Condenser air leaving temp
- OD ambience (Condenser air inbound temp)
- Condensing temp (not pressure...from PT Chart)
- Liquid line Temp
- Suction line temp at Evaporator outlet (to calculate evaporator SH)
- Evaporating temp (not Pressure...from PT Chart)
- Suction line temp at Compressor (to evaluate compressor cooling Maximum temp at normal operation conditions = 70 deg F)
- Belch line Temp (Oil breakup if over 270 deg F...Spit test)
Calculations:
Evaporator air split =#1 - #2
Condenser air split up =#four - #v
Subcooling = #6 - #7 (10 to 15 deg F Normal for any type of metering device)
Superheat = #8 - #nine (x-12 deg F for TXV and for Cap tube or orifice at NORMAL operating loads)
Suction line temp at compressor (at least lxx deg F for compressor cooling and no less than 5 deg F SH at compressor inlet to foreclose liquid flooding.)"I take never let my schooling interfere with my education."
Marker Twain
NEVER STOP LEARNING.
-
Post Likes - 1 Likes, 0 Dislikes
-
Originally Posted by beenthere
- I concur, however in my ARIZONA feel, I have NO feel in high ambience humidity.
- Also I would add that airflow matters a lot. The testing by Arizona Public Service (utility) adamant that the average airflow of the average Air-conditioning in their testing was nether 325 CFM per ton which they cited as the manufacturer's minimum airflow.
"I have never let my schooling interfere with my education."
Marking Twain
NEVER End LEARNING.
-
Mail service Likes - 1 Likes, 0 Dislikes
-
Originally Posted by lynn comstock
-
Originally Posted by beenthere
The SH charts utilize to cap tube and orifice systems only. The TXV systems establish a stock-still SH once there is plenty refrigerant to fill the liquid line...Then SC tells you when to cease calculation refrigerant. I'd say, xv deg F is max."I accept never let my schooling interfere with my pedagogy."
Mark Twain
NEVER Stop LEARNING.
-
Originally Posted by BrownPigeonSwag
*********
https://www.hvac20.com/ High efficiency equipment alone does not provide home comfort and efficiency. HVAC2.0 is a procedure for finding the existent needs of the house and the occupants. Offer the client a carte du jour of piece of work to address their bug and give them a probability of success.Find contractors with specialized training in combustion analysis, residential system performance, air menstruation, and duct optimization
https://www.myhomecomfort.org/
Site member map Here!
Source: https://hvac-talk.com/vbb/threads/2162631-067-sized-piston-unit-calls-for-070-Is-this-enough-to-cause-issues
0 Response to "what size orifice to use with 407c in a 5 ton"
Post a Comment